Current
transformer- Definition, Principle, Equivalent circuit and types.
A current
transformer is an “Instrument
transformer”, used along with measuring or protective devices, in which the
secondary current is proportional to the primary current (under normal
conditions of operation) and differs from it by an angle which is approximately
zero.
Current
transformers perform the following functions:
·
Current
transformers supply the protective relays with currents of magnitude proportional
to those of power circuit but sufficiently reduced in magnitude.
·
The
measuring devices cannot be directly connected to the high magnitude supplies.
Hence current transformers are used to supply those devices with currents of
magnitude proportional to those of power.
·
A
current transformer also isolates the measuring instruments from high voltage circuits..
Principle:-
The basic
principle of current transformer is same as that of the power transformer. Like
the power transformer current transformer also contains a primary and a
secondary winding. Whenever an alternating current flows through the primary winding
alternating magnetic flux is produced, which then induces alternating current in
the secondary winding.
In case of
current transformers the load impedance or “burden” is very small. Therefore
the current transformer operates under short circuit conditions. Also the
current in the secondary winding does not depend load impedance but depends on
the current flowing in the primary winding. The current transformer basically
consists of an iron core on which primary winding and secondary winding are
wound.
The primary
winding of the transformer is connected in series with the load and carries the
actual current flowing to the load while the secondary winding is connected to
a measuring device or a relay. The number of secondary turns is proportional to
the current flowing through the primary. (i.e.) larger the magnitude of current
flowing through the primary, more the number of secondary turns.
The ratio of
primary current to the secondary current is known as the current transformation
ratio of the CT. Usually the current transformation ratio of the CT is high. Normally
the secondary ratings are of the order 5 A, 1 A, 0.1 A whereas the primary rating
vary from 10 A to 3000 A or more. The CT handles very less power.
Rated burden can be defines
as the product of current and voltage at the secondary side of the CT. It is
measured in volt ampere (VA). The secondary of a current transformer should not
be disconnected from its Rated burden while current is flowing in the primary. As
the primary current is independent of the secondary current, the entire primary
current acts as a magnetizing current when secondary is opened. This results in
deep saturation of the core which cannot return to normal state and so the CT
is no longer usable.
Types of Current
transformers:-
Based on the function performed
by the current transformer it can be classified in to as follows:
1. Measuring
current transformers:-
·
These
current transformers are used along with the measuring devices for the
measurement of current, energy and power.
2. Protective
current transformers:-
·
These
current transformers are used along with the protection equipments such as trip
coils, relays etc.
Based
on the function construction it can be classified in to as follows:
1) Bar Type: This type of
current transformer consists of a bar of suitable size and Material forming an
integral part of the transformer.
2) Wound Type: This type of CTs
have a primary winding of more than one full turn Wound over the core.
3) Window Type: CTs of this type
have no primary winding. The secondary wind of the CT is placed around the
current flowing conductor. The magnetic electric field created by current
flowing through the conductor induces current in the secondary winding which is
used for measurement.
Secondary
current rating:-
The value of
rated secondary current is 5A. the secondary current rating of 2A and 1A may
also be used in some cases if the number of secondary turns is low the ratio
cannot be adjusted within the required limits by addition or removal of one
turn, if the length of secondary connecting lead is such that the burden due to
them at higher secondary current would be excessive.
The disadvantage
of making transformer with lower secondary current rating are that they produce
much higher voltage if they are ever accidentally left open circuited. For this
reason it is better to adopt 5 A rating at the secondary.
Terminology of
current transformer:-
Rated
transformation ratio:
·
Rated
transformation ratio is defines as the ratio of the rated primary current to
the rated secondary current.
Current error
(ratio error):
·
The
percentage error in the magnitude of the secondary current is defined by the
following formula
·
Ratio
error = (KnIs - Ip)/ Ip x 100%
·
Ip,
Is = primary and secondary winding currents respectively,
·
Kn
= turns ratio
Accuracy class:
·
It
is a classification assigned to a transformer. In the case of metering CT’s,
accuracy class shall be 2, 0.5, 1.3 and 5.
Phase
displacement:
·
The
difference in phase between the primary and the secondary current phasors, the
direction of the phasors being chosen such that the angle is zero for a perfect
transformer.
Rated secondary
current:
·
The
value of rated secondary current shall be 5 A. The secondary currents rating of
2 and 1 A may also be used in some case.
Rated burden:
·
The
product of current and voltage at the secondary side of the CT is called as
rated burden. It is measured in volt ampere (VA).
Temperature rise:
·
The
temperature rise of current transformer winding when carrying a rated primary
current, at rated frequency and with rated burden should not exceed the
approximate values given in table.
No comments:
Post a Comment