Translate

Monday, 21 August 2023

Top 6 Interview Questions ~ ELECTRICAL AUTOCAD INTERVIEW QUESTIONS

 1.What is the circuit diagram?

A circuit diagram is derived from a functional layout and It doesn’t generally bear any relationship to the physical shape, size or layout of the parts and although you’ll wire up an assembly from the knowledge given in it, they’re usually intended to point out the detail of how an circuit works.

1) Symbols to represent the components;

2) Lines to represent the functional conductors or wires which connect them together.

2. What is wiring diagram?

Wiring diagram is the drawing which shows all the wiring between the parts such as:

1) Control or signal functions;

2) Power supplies and earth connections;

3) Termination of unused leads, contacts;

4) Interconnection via terminal posts, blocks, plugs, sockets, lead-throughs.

3. What is wiring schedule?

A wiring schedule defines the wire reference number, type, length and the amount of insulation stripping required for soldering.

In complex equipment you’ll also find a table of interconnections which can give the starting and finishing reference points of every connection also as other important information such as wire colour, identification marking then on.

4. What is block diagram?

The diagram is afunctional drawing which is employed to point out and describe the most operating principles of the equipment and is typically drawn before the circuit diagram. It will not give any detail of the actual wiring connections or even the smallest components.

5. List the Electrical Templates?

The template files that start with ACE are electrical drawing templates. ACAD_Electrical.dwt and ACAD_Electrical_IEC.dwt are the electrical templates used for creating AutoCAD Electrical drawings.

6. What is Project Manager?

Project Manager is used to list the drawing files associated with each open project.

New drawings can be added, reorder drawing files project settings can be changed.


Saturday, 21 March 2020

Differential Relay | Transformer Differential | Line Differential | Differential relay concept

Differential relays are very sensitive to the faults occurred within the zone of protection but they are least sensitive to the faults that occur outside the protected zone. Most of the relays operate when any quantity exceeds beyond a predetermined value for example over current relay operates when current through it exceeds predetermined value. But the principle of differential relay is somewhat different. It operates depending upon the difference between two or more similar electrical quantities.

Definition of Differential Relay

The differential relay is one that operates when there is a difference between two or more similar electrical quantities exceeds a predetermined value. In the differential relay scheme circuit, there are two currents come from two parts of an electrical power circuit. These two currents meet at a junction point where a relay coil is connected. According to Kirchhoff Current Law, the resultant current flowing through the relay coil is nothing but the summation of two currents, coming from two different parts of the electrical power circuit. If the polarity and amplitude of both the currents are so adjusted that the phasor sum of these two currents, is zero at normal operating condition. Thereby there will be no current flowing through the relay coil at normal operating conditions. But due to any abnormality in the power circuit, if this balance is broken, that means the phasor sum of these two currents no longer remains zero and there will be non-zero current flowing through the relay coil thereby relay being operated.
In the current differential scheme, there are two sets of current transformer each connected to either side of the equipment protected by differential relay. The ratio of the current transformers are so chosen, the secondary currents of both current transformers matches each other in magnitude.

The polarities of current transformers are such that the secondary current of these CTs opposes each other. From the circuit is clear that only if any nonzero difference is created between this to secondary currents, then only this differential current will flow through the operating coil of the relay. If this difference is more than the peak up value of the relay, it will operate to open the circuit breakers to isolate the protected equipment from the system. The relaying element used in differential relay is attracted armature type instantaneously relay since differential scheme is only adapted for clearing the fault inside the protected equipment in other words differential relay should clear only the internal fault of the equipment hence the protected equipment should be isolated as soon as any fault occurred inside the equipment itself. They need not be any time delay for coordination with other relays in the system.

Types of Differential Relay

There are mainly two types of differential relay depending upon the principle of operation.
  1. Current Balance Differential Relay
  2. Voltage Balance Differential Relay
In current differential relay two current transformers are fitted on the either side of the equipment to be protected. The secondary circuits of CTs are connected in series in such a way that they carry secondary CT current in same direction.
The operating coil of the relaying element is connected across the CT’s secondary circuit. Under normal operating conditions, the protected equipment (either power transformer or alternator) carries normal current. In this situation, say the secondary current of CT1 is I1 and secondary current of CT2 is I2. It is also clear from the circuit that the current passing through the relay coil is nothing but I1-I2. As we said earlier, the current transformer’s ratio and polarity are so chosen, I1 = I2, hence there will be no current flowing through the relay coil. Now if any fault occurs in the external to the zone covered by the CTs, faulty current passes through primary of the both current transformers and thereby secondary currents of both current transformers remain same as in the case of normal operating conditions. Therefore at that situation the relay will not be operated. But if any ground fault occurred inside the protected equipment as shown, two secondary currents will be no longer equal. At that case the differential relay is being operated to isolate the faulty equipment (transformer or alternator) from the system.


Principally this type of relay systems suffers from some disadvantages
  1. There may be a probability of mismatching in cable impedance from CT secondary to the remote relay panel.
  2. These pilot cables’ capacitance causes incorrect operation of the relay when large through fault occurs external to the equipment.
  3. Accurate matching of characteristics of current transformer cannot be achieved hence there may be spill current flowing through the relay in normal operating conditions.

Percentage Differential Relay

This is designed to response to the differential current in the term of its fractional relation to the current flowing through the protected section. In this type of relay, there are restraining coils in addition to the operating coil of the relay. The restraining coils produce torque opposite to the operating torque. Under normal and through fault conditions, restraining torque is greater than operating torque. Thereby relay remains inactive. When internal fault occurs, the operating force exceeds the bias force and hence the relay is operated. This bias force can be adjusted by varying the number of turns on the restraining coils. As shown in the figure below, if I1 is the secondary current of CT1 and I2 is the secondary current of CT2 then current through the operating coil is I1 – I2 and current through the restraining coil is (I1 + I2)/2. In normal and through fault condition, torque produced by restraining coils due to current (I1+ I2)/2 is greater than torque produced by operating coil due to current I1– I2 but in internal faulty condition these become opposite. And the bias setting is defined as the ratio of (I1– I2) to (I1+ I2)/2.




It is clear from the above explanation, greater the current flowing through the restraining coils, higher the value of the current required for operating coil to be operated. The relay is called percentage relay because the operating current required to trip can be expressed as a percentage of through current.

CT Ratio and Connection for Differential Relay

This simple thumb rule is that the current transformers on any star winding should be connected in delta and the current transformers on any delta winding should be connected in star. This is so done to eliminate zero sequence current in the relay circuit.


If the CTs are connected in star, the CT ratio will be In/1 or 5 A

CTs to be connected in delta, the CT ratio will be In/0.5775 or 5×0.5775 A

Voltage Balance Differential Relay

In this arrangement the current transformer are connected either side of the equipment in such a manner that EMF induced in the secondary of both current transformers will oppose each other. That means the secondary of the current transformers from both sides of the equipment are connected in series with opposite polarity. The differential relay coil is inserted somewhere in the loop created by series connection of secondary of current transformers as shown in the figure. In normal operating conditions and also in through fault conditions, the EMFs induced in both of the CT secondary are equal and opposite of each other and hence there would be no current flowing through the relay coil. But as soon as any internal fault occurs in the equipment under protection, these EMFs are no longer balanced hence current starts flowing through the relay coil thereby trips circuit breaker.

Thursday, 15 August 2019

Electrical Fault Calculation | Positive Negative Zero Sequence Impedance

Before applying proper electrical protection system, it is necessary to have through knowledge of the conditions of electrical power system during faults. The knowledge of electrical fault condition is required to deploy proper different protective relays in different locations of electrical power system.
Information regarding values of maximum and minimum fault currents, voltages under those faults in magnitude and phase relation with respect to the currents at different parts of power system, to be gathered for proper application of protection relay system in those different parts of the electrical power system. Collecting the information from different parameters of the system is generally known as electrical fault calculation.
Fault calculation broadly means calculation of fault current in any electrical power system. There are mainly three steps for calculating faults in a system.
  1. Choice of impedance rotations.
  2. Reduction of complicated electrical power system network to single equivalent impedance.
  3. Electrical fault currents and voltages calculation by using symmetrical component theory.

Impedance Notation of Electrical Power System

If we look at any electrical power system, we will find, these are several voltage levels. For example, suppose a typical power system where electrical power is generated at 6.6 kV then that 132 kV power is transmitted to terminal substation where it is stepped down to 33 kV and 11 kV levels and this 11 kV level may further step down to 0.4 kv.
Hence from this example it is clear that a same power system network may have different voltage levels. So calculation of fault at any location of the said system becomes much difficult and complicated it try to calculate impedance of different parts of the system according to their voltage level. This difficulty can be avoided if we calculate impedance of different part of the system in reference to a single base value. This technique is called impedance notation of power system. In other wards, before electrical fault calculation, the system parameters, must be referred to base quantities and represented as uniform system of impedance in either ohmic, percentage, or per unit values.
Electrical power and voltage are generally taken as base quantities. In three phase system, three phase power in MVA or KVA is taken as base power and line to line voltage in KV is taken as base voltage. The base impedance of the system can be calculated from these base power and base voltage, as follows,
Per unit is an impedance value of any system is nothing but the radio of actual impedance of the system to the base impedance value.
Percentage impedance value can be calculated by multiplying 100 with per unit value.

Again it is sometimes required to convert per unit values referred to new base values for simplifying different electrical fault calculations. In that case,

The choice of impedance notation depends upon the complicity of the system. Generally base voltage of a system is so chosen that it requires minimum number of transfers.
Suppose, one system as a large number of 132 KV over head lines, few numbers of 33 KV lines and very few number of 11 KV lines. The base voltage of the system can be chosen either as 132 KV or 33 KV or 11 KV, but here the best base voltages 132 KV, because it requires minimum number of transfer during fault calculation.
Network Reduction
After choosing the correct impedance notation, the next step is to reduce network to a single impedance. For this first we have to convert the impedance of all generators, lines, cables, transformer to a common base value. Then we prepare a schematic diagram of electrical power system showing the impedance referred to same base value of all those generators, lines, cables and transformers.
The network then reduced to a common equivalent single impedance by using star/delta transformations. Separate impedance diagrams should be prepared for positive, negative and zero sequence networks.
There phase faults are unique since they are balanced i.e. symmetrical in three phase, and can be calculated from the single phase positive sequence impedance diagram. Therefore three phase fault current is obtained by,

Where, I f is the total three phase fault current, v is the phase to neutral voltage z 1 is the total positive sequence impedance of the system; assuming that in the calculation, impedance are represented in ohms on a voltage base.



Symmetrical Component Analysis

The above fault calculation is made on assumption of three phase balanced system. The calculation is made for one phase only as the current and voltage conditions are same in all three phases. When actual faults occur in electrical power system, such as phase to earth fault, phase to phase fault and double phase to earth fault, the system becomes unbalanced means, the conditions of voltages and currents in all phases are no longer symmetrical. Such faults are solved by symmetrical component analysis. Generally three phase vector diagrammay be replaced by three sets of balanced vectors. One has opposite or negative phase rotation, second has positive phase rotation and last one is co-phasal. That means these vectors sets are described as negative, positive and zero sequence, respectively.positive negative zero sequence voltage
The equation between phase and sequence quantities are,

Therefore,

Where all quantities are referred to the reference phase r.
Similarly a set of equations can be written for sequence currents also. From, voltage and current equations, one can easily determine the sequence impedance of the system. The development of symmetrical component analysis depends upon the fact that in balanced system of impedance, sequence currents can give rise only to voltage drops of the same sequence. Once the sequence networks are available, these can be converted to single equivalent impedance.
Let us consider Z1, Z2 and Z0 are the impedance of the system to the flow of positive, negative and zero sequence current respectively.
For earth fault

Phase to phase faults


Double phase to earth faults

Three phase faults

If fault current in any particular branch of the network is required, the same can be calculated after combining the sequence components flowing in that branch. This involves the distribution of sequence components currents as determined by solving the above equations, in their respective network according to their relative impedance. Voltages it any point of the network can also be determine once the sequence component currents and sequence impedance of each branch are known.
Sequence Impedance
Positive Sequence Impedance
The impedance offered by the system to the flow of positive sequence current is called positive sequence impedance.

Negative Sequence Impedance

The impedance offered by the system to the flow of negative sequence current is called negative sequence impedance.

Zero Sequence Impedance

The impedance offered by the system to the flow of zero sequence current is known as zero sequence impedance.
In previous fault calculation, Z1, Z2 and Z0 are positive, negative and zero sequence impedance respectively. The sequence impedance varies with the type of power system components under consideration:-
  1. In static and balanced power system components like transformer and lines, the sequence impedance offered by the system are the same for positive and negative sequence currents. In other words, the positive sequence impedance and negative sequence impedance are same for transformers and power lines.
  2. But in case of rotating machines the positive and negative sequence impedance are different.
  3. The assignment of zero sequence impedance values is a more complex one. This is because the three zero sequence current at any point in a electrical power system, being in phase, do not sum to zero but must return through the neutral and /or earth. In three phase transformer and machine fluxes due to zero sequence components do not sum to zero in the yoke or field system. The impedance very widely depending upon the physical arrangement of the magnetic circuits and winding.
    1. The reactance of transmission lines of zero sequence currents can be about 3 to 5 times the positive sequence current, the lighter value being for lines without earth wires. This is because the spacing between the go and return(i.e. neutral and/or earth) is so much greater than for positive and negative sequence currents which return (balance) within the three phase conductor groups.
    2. The zero sequence reactance of a machine is compounded of leakage and winding reactance, and a small component due to winding balance (depends on winding tritch).
    3. The zero sequence reactance of transformers depends both on winding connections and upon the construction of the core.

Faraday’s Laws of Electromagnetic Induction: First & Second Law

What is Faraday’s Law

Faraday’s law of electromagnetic induction (referred to as Faraday’s law) is a basic law of electromagnetism predicting how a magnetic field will interact with an electric circuit to produce an electromotive force (EMF). This phenomenon is known as electromagnetic induction.
Faraday’s law states that a current will be induced in a conductor which is exposed to a changing magnetic field. Lenz’s law of electromagnetic induction states that the direction of this induced current will be such that the magnetic field created by the induced current opposes the initial changing magnetic field which produced it. The direction of this current flow can be determined using Fleming’s right-hand rule.
Faraday’s law of induction explains the working principle of transformers, motors, generators, and inductors. The law is named after Michael Faraday, who performed an experiment with a magnet and a coil. During Faraday’s experiment, he discovered how EMF is induced in a coil when the flux passing through the coil changes.

Faraday’s Experiment

In this experiment, Faraday takes a magnet and a coil and connects a galvanometer across the coil. At starting, the magnet is at rest, so there is no deflection in the galvanometer i.e the needle of the galvanometer is at the center or zero position. When the magnet is moved towards the coil, the needle of the galvanometer deflects in one direction.
When the magnet is held stationary at that position, the needle of galvanometer returns to zero position. Now when the magnet moves away from the coil, there is some deflection in the needle but opposite direction, and again when the magnet becomes stationary, at that point respect to the coil, the needle of the galvanometer returns to the zero position. Similarly, if the magnet is held stationary and the coil moves away, and towards the magnet, the galvanometer similarly shows deflection. It is also seen that the faster the change in the magnetic field, the greater will be the induced EMF or voltagein the coil.
Position of magnetDeflection in galvanometer
Magnet at restNo deflection in the galvanometer
Magnet moves towards the coilDeflection in galvanometer in one direction
Magnet is held stationary at same position (near the coil)No deflection in the galvanometer
Magnet moves away from the coilDeflection in galvanometer but in the opposite direction
Magnet is held stationary at the same position (away from the coil)No deflection in the galvanometer
Conclusion: From this experiment, Faraday concluded that whenever there is relative motion between a conductor and a magnetic field, the flux linkage with a coil changes and this change in flux induces a voltage across a coil.
Michael Faraday formulated two laws on the basis of the above experiments. These laws are called Faraday’s laws of electromagnetic induction.

Faraday’s First Law

Any change in the magnetic field of a coil of wire will cause an emf to be induced in the coil. This emf induced is called induced emf and if the conductor circuit is closed, the current will also circulate through the circuit and this current is called induced current.
Method to change the magnetic field:
  1. By moving a magnet towards or away from the coil
  2. By moving the coil into or out of the magnetic field
  3. By changing the area of a coil placed in the magnetic field
  4. By rotating the coil relative to the magnet
Michael Faraday

Faraday’s Second Law

It states that the magnitude of emf induced in the coil is equal to the rate of change of flux that linkages with the coil. The flux linkage of the coil is the product of the number of turns in the coil and flux associated with the coil.

Faraday Law Formula

Faraday's Law Formula
Consider, a magnet is approaching towards a coil. Here we consider two instants at time T1 and time T2.
Flux linkage with the coil at time,
Flux linkage with the coil at time,
Change in flux linkage,
Let this change in flux linkage be,
So, the Change in flux linkage
Now the rate of change of flux linkage
Take derivative on right-hand side we will get
The rate of change of flux linkage
But according to Faraday’s law of electromagnetic induction, the rate of change of fluxlinkage is equal to induced emf.
Considering Lenz’s Law.
Where:
  • Flux Φ in Wb = B.A
  • B = magnetic field strength
  • A = area of the coil

How To Increase EMF Induced in a Coil

  • By increasing the number of turns in the coil i.e N, from the formulae derived above it is easily seen that if the number of turns in a coil is increased, the induced emf also gets increased.
  • By increasing magnetic field strength i.e B surrounding the coil- Mathematically, if magnetic field increases, flux increases and if flux increases emf induced will also get increased. Theoretically, if the coil is passed through a stronger magnetic field, there will be more lines of force for the coil to cut and hence there will be more emf induced.
  • By increasing the speed of the relative motion between the coil and the magnet – If the relative speed between the coil and magnet is increased from its previous value, the coil will cut the lines of flux at a faster rate, so more induced emf would be produced.

Applications of Faraday’s Law

Faraday law is one of the most basic and important laws of electromagnetism. This law finds its application in most of the electrical machines, industries, and the medical field, etc.
  • Power transformers function based on Faraday’s law
  • The basic working principle of the electrical generator is Faraday’s law of mutual induction.
  • The Induction cooker is the fastest way of cooking. It also works on the principle of mutual induction. When current flows through the coil of copper wire placed below a cooking container, it produces a changing magnetic field. This alternating or changing magnetic field induces an emf and hence the current in the conductive container, and we know that the flow of current always produces heat in it.
  • Electromagnetic Flow Meter is used to measure the velocity of certain fluids. When a magnetic field is applied to an electrically insulated pipe in which conducting fluids are flowing, then according to Faraday’s law, an electromotive force is induced in it. This induced emf is proportional to the velocity of fluid flowing.
  • Form bases of Electromagnetic theory, Faraday’s idea of lines of force is used in well known Maxwell’s equations. According to Faraday’s law, change in magnetic field gives rise to change in electric field and the converse of this is used in Maxwell’s equations.
  • It is also used in musical instruments like an electric guitar, electric violin, etc.

Lenz’s Law of Electromagnetic Induction: Definition & Formula

What is Lenz’s Law?

Lenz’s law of electromagnetic induction states that the direction of the current induced in a conductor by a changing magnetic field (as per Faraday’s law of electromagnetic induction) is such that the magnetic field created by the induced current opposes the initial changing magnetic field which produced it. The direction of this current flow is given by Fleming’s right hand rule.
This can be hard to understand at first – so let’s look at an example problem. Remember that when a current is induced by a magnetic field, the magnetic field that this induced current produces will create its own magnetic field. This magnetic field will always be such that it opposes the magnetic field that originally created it. In the example below, if the magnetic field “B” is increasing – as shown in (1) – the induced magnetic field will act in opposition to it.

When the magnetic field “B” is decreasing – as shown in (2) – the induced magnetic field will again act in opposition to it. But this time ‘in opposition’ means that it is acting to increase the field – since it is opposing the decreasing rate of change.
Lenz’s law is based on Faraday’s law of induction. Faraday’s law tells us that a changing magnetic field will induce a current in a conductor. Lenzs law tells us the direction of this induced current, which opposes the initial changing magnetic field which produced it. This is signified in the formula for Faraday’s law by the negative sign (‘–’).
Lenz's Law Equation
This change in the magnetic field may be caused by changing the magnetic field strength by moving a magnet towards or away from the coil, or moving the coil into or out of the magnetic field. In other words, we can say that the magnitude of the EMF induced in the circuit is proportional to the rate of change of flux.

Lenz’s Law Formula

Lenz’s law states that when an EMF is generated by a change in magnetic fluxaccording to Faraday’s Law, the polarity of the induced EMF is such, that it produces an induced current whose magnetic field opposes the initial changing magnetic field which produced it
The negative sign used in Faraday’s law of electromagnetic induction, indicates that the induced EMF (ε) and the change in magnetic flux (δΦB) have opposite signs. The formula for Lenz’s law is shown below:
Lenz's Law Formula
Where:
  • ε = Induced emf
  • δΦB = change in magnetic flux
  • N = No of turns in coil

Lenz’s Law and Conservation of Energy

To obey the conservation of energy, the direction of the current induced via Lenz’s law must create a magnetic field that opposes the magnetic field that created it. In fact, Lenz’s law is a consequence of the law of conservation of energy.
Why’s that you ask? Well, let’s pretend that wasn’t the case and see what happens.
If the magnetic field created by the induced current is the same direction as the field that produced it, then these two magnetic fields would combine and create a larger magnetic field. This combined larger magnetic field would, in turn, induce another current within the conductor twice the magnitude of the original induced current.
And this would, in turn, create another magnetic field which would induce yet another current. And so on. So we can see that if Lenz’s law did not dictate that the induced current must create a magnetic field that opposes the field that created it – then we would end up with an endless positive feedback loop, breaking the conservation of energy (since we are effectively creating an endless energy source).
Lenz’s law also obeys Newton’s third law of motion (i.e to every action there is always an equal and opposite reaction). If the induced current creates a magnetic field which is equal and opposite to the direction of the magnetic field that creates it, then only it can resist the change in the magnetic field in the area. This is in accordance with Newton’s third law of motion.

Lenz’s Law Explained

To better understand Lenz’s law, let us consider two cases:
Case 1: When a magnet is moving towards the coil.
What is Lenz Law
When the north pole of the magnet is approaching towards the coil, the magnetic flux linking to the coil increases. According to Faraday’s law of electromagnetic induction, when there is a change in flux, an EMF and hence current is induced in the coil and this current will create its own magnetic field.
Now according to Lenz’s law, this magnetic field created will oppose its own or we can say opposes the increase in flux through the coil and this is possible only if approaching coil side attains north polarity, as we know similar poles repel each other. Once we know the magnetic polarity of the coil side, we can easily determine the direction of the induced current by applying right hand rule. In this case, the current flows in the anticlockwise direction.
Case 2: When a magnet is moving away from the coil
Lenz Law Definition
When the north pole of the magnet is moving away from the coil, the magnetic flux linking to the coil decreases. According to Faraday’s law of electromagnetic induction, an EMF and hence current is induced in the coil and this current will create its own magnetic field.
Now according to Lenz’s law, this magnetic field created will oppose its own or we can say opposes the decrease in flux through the coil and this is possible only if approaching coil side attains south polarity, as we know dissimilar poles attract each other. Once we know the magnetic polarity of the coil side, we can easily determine the direction of the induced current by applying right hand rule. In this case, the current flows in a clockwise direction.
Note that for finding the directions of magnetic field or current, use the right-hand thumb rule i.e if the fingers of the right hand are placed around the wire so that the thumb points in the direction of current flow, then the curling of fingers will show the direction of the magnetic field produced by the wire.
Fleming’s Right Hand Rule
Lenzs law can be stated as follows:
  • If the magnetic flux Ф linking a coil increases, the direction of current in the coil will be such that it will oppose the increase in flux and hence the induced current will produce its flux in a direction as shown below (using Fleming’s right-hand thumb rule)
State Lenz Law
  • If magnetic flux Ф linking a coil is decreasing, the flux produced by the current in the coil is such, that it will aid the main flux and hence the direction of current is as shown below.
Define Lenz Law

Lenz’s Law Applications

The applications of Lenz’s law include:
  • Lenz’s law can be used to understand the concept of stored magnetic energy in an inductor. When a source of emf is connected across an inductor, a current starts flowing through it. The back emf will oppose this increase in current through the inductor. In order to establish the flow of current, the external source of emf has to do some work to overcome this opposition. This work can be done by the emf is stored in the inductor and it can be recovered after removing the external source of emf from the circuit
  • This law indicates that the induced emf and the change in flux have opposite signs which provide a physical interpretation of the choice of sign in Faraday’s law of induction.
  • Lenz’s law is also applied to electric generators. When a current is induced in a generator, the direction of this induced current is such that it opposes and causes rotation of generator (as in accordance to Lenz’s law) and hence the generator requires more mechanical energy. It also provides back emf in case of electric motors.
  • Lenz’s law is also used in electromagnetic braking and induction cooktops.

State Lenz’s Law

Lenz’s law states that the direction of the current induced in a conductor by a changing magnetic field is such that the magnetic field created by the induced current opposes the initial changing magnetic field which produced it.
Lenz’s Law
Lenz’s Law is named after the German scientist H. F. E. Lenz in 1834. Lenz’s law obeys Newton’s third law of motion (i.e to every action there is always an equal and opposite reaction) and the conservation of energy (i.e energy may neither be created nor destroyed and therefore the sum of all the energies in the system is a constant).